產(chǎn)品型號:BCJ10
2*3W消防應(yīng)急LED防爆應(yīng)急燈應(yīng)急燈中正常照明燈和應(yīng)急照明燈各自獨立,適合安 裝條件許可的場所;照明應(yīng)急兩用燈,正常照明和應(yīng)急照明 共用一個燈體,光源獨立. 內(nèi)裝免維護鎳鎘電池組,在正常供電下自動充電,事故斷 電或停電時應(yīng)急燈自動點亮。 鋼管或電纜布線
All emergency lamps and lanterns should be equipped with special lines without switches. Two wire and three wire emergency lamps can be unified on the special power supply. The setting of each special power supply should be combined with the corresponding fire protection standard. If the emergency power supply and lamps rotate separately, high temperature resistant wires shall be used for electrical connection to meet the fire protection requirements.
2*3W消防應(yīng)急LED防爆應(yīng)急燈接線方法
各應(yīng)急燈具宜設(shè)置線路,中途不設(shè)置開關(guān)。二線制和三線制型應(yīng)急燈具可統(tǒng)一在電源上。各電源的設(shè)置應(yīng)和相應(yīng)的防火標準結(jié)合。應(yīng)急電源與燈具分開旋轉(zhuǎn)的,其電氣連接應(yīng)采用耐高溫電線,以滿足防火要求。
二線制
該接法是應(yīng)急燈具常用接法,適用在應(yīng)急燈平時不作照明使用或24小時持續(xù)照明用(CED標志燈就屬于此品種),待斷電后,應(yīng)急燈主動點亮。
三線制
連接法為應(yīng)急燈常用的接法,可對應(yīng)急燈具平時照明狀況的開或關(guān)進行操控,當電網(wǎng)斷電時不管開關(guān)處于何種狀況,應(yīng)急燈當即點亮應(yīng)急。K為平時照明開關(guān)。
應(yīng)急燈中正常照明燈和應(yīng)急照明燈各自獨立,合適安
裝條件答應(yīng)的場所;照明應(yīng)急兩用燈,正常照明和應(yīng)急照明
共用一個燈體,光源獨立.
內(nèi)裝免維護鎳鎘電池組,在正常供電下主動充電,事端斷
電或停電時應(yīng)急燈主動點亮。
鋼管或電纜布線均可。
可根據(jù)用戶要求設(shè)置實驗按鈕和指示燈具
1、電池充電電路
外電源經(jīng)Q2,Q6,R8,D10對電池進行恒流充電。當有外電源供電時,充電電流經(jīng)R8,D10向電池充電,且使充電指示燈D12點亮。
2、燈操控電路
由Q3,仍、Q5、Q7和鍵K,G構(gòu)成,在無市電時,按一下K(開)鍵,Q5飽滿導通,Q5的集電極電流通過R12使Q7維持導通;D11反向擊穿作業(yè)在穩(wěn)壓狀況,Q5的集電極電壓給Q3,Q4供給偏置使其導通,點亮L1、L2。當按一下G(關(guān))鍵時,Q7截止,撤除了Q5導通條件,燈封閉。
2*3W消防應(yīng)急LED防爆應(yīng)急燈當有市電供電時,外電源經(jīng)D9使D7反向截止,Q5無法導通,鍵K和G都不能操控燈Ll,L2的開和關(guān)。停電后二極管D7負極電位變?yōu)榱悖蛊渌查g正導游通,Q5飽滿導通,構(gòu)成點燈電路條件,L1、L2點亮。來一電后D7負極電位變高又反向截止,Q5截止,燈滅(起到主動操控的效果)。點燈操控電路中D7、Q7通過R6作業(yè)在臨界狀況,開要害K,G只起到觸發(fā)效果。
3、實驗電路
當按住實驗按鍵S不放時,Ql截止,D7負極電位變低而正偏導通,使Q5導通滿足點燈條件,使L1、L2點亮。松開S鍵燈隨即熄滅。實驗電路的效果是測驗點燈電路是否芷常。
4、電源電路
220V交流經(jīng)變壓器變壓,整流濾波,由Ql集電極輸出4.6V的直流電壓。首要供給給充電電路給電池充電。并經(jīng)R9使D14發(fā)光指示。